AbstractIn the early experiments of the LHD, the harmful third harmonic currents had been observed in the power line of the NIFS substation, when the fly-wheel motor generator (MG) for the neutral beam injection (NBI) reaccelerates between the plasma productions. The variable harmonic currents, which were estimated to be 1±6 and 1±12 ns, were induced through a Scherbius device. They extremely resonated to the circuit impedance of the power line. To stabilize electrical power in the site, following modifications were conducted: (1) reduction of the harmonic current from the Scherbius device; (2) reconnection of the power supplies of the SC coils and heating devices to suitable power feeders; (3) compensation of lagging reactive power of the MG. As a result, harmful harmonic currents were suppressed.
初期のLHD実験において、プラズマ生成の合間にフライホイール・モータージェネレータ(MG)が再加速する際、NIFS変電所の電力線に有害な高調波電流が観測された。この高調波電流は、中性粒子ビーム入射(NBI)用のセルビウス装置を介して誘起され、その時間幅は1±6 nsおよび1±12 nsと推定された。これらの高調波は、電力線の回路インピーダンスと強く共振し、電力系統の安定性を損なう要因となった。この問題を解決するため、以下の対策が実施された:(1) セルビウス装置からの高調波電流の低減、(2) SCコイルおよび加熱装置の電源を適切なフィーダーへ接続し直すこと、(3) MGの遅れ無効電力の補償。これらの対策により、有害な高調波電流は効果的に抑制された。