AbstractTo investigate properties of superconducting R&D conductors and coils for the Large Helical Device (LHD), a dc 75 kA power supply system which consists of three 25 kA unit banks has been designed and constructed. One unit bank has two double-star-rectifier connections with the inter-phase reactors. The algorithm of the digital feedback control system is installed in each unit bank. In this algorithm, each 6 phase is operated independently on the process of averaging, proportioning and integrating. The experiments of several short samples and one of the R&D coils have been done under the maximum ramp rate of the power supply, 999 A/s per unit. It is confirmed that the measured current stability is less than ±0.75%, and the deviation between a set value and an output value of the load current is less than ±1% under the short circuit test.
大型ヘリカル装置(LHD)用の超伝導R&D導体の特性を調査するために、3基の25 kAユニットバンクから構成される直流75 kA電源システムが設計・建設された。1ユニットバンクは、相間リアクトルを備えた2組の二重星形整流器接続を有する。デジタルフィードバック制御のアルゴリズムが各ユニットバンクに実装されている。このアルゴリズムでは、各6相が平均化、比例、積分のプロセスに基づいて独立して動作する。複数の短尺試料と1つのR&Dコイルを用いた実験が、電源の最大昇磁速度999 A/s(ユニットバンクあたり)の条件下で実施された。測定された電流安定度は±0.75%以内であり、短絡試験における負荷電流の設定値と出力値の偏差は±1%以内であることが確認された。